Indoor Air Quality Monitoring Guidance for Schools
An evidence-based checklist for your schoolLearn how IAQ monitors can help schools assess ventilation, track air quality conditions and support decision-making.
What Are IAQ Monitors?
Low-cost air quality monitors (also referred to as air pollution monitors, air sensors, air quality sensors, air pollutant meters or detectors, or similar) are devices that use one or more sensors to detect, monitor, and report on specific air pollutants and/or environmental factors.
Schools can utilize continuous indoor air quality (IAQ) monitoring to:
- Collect real-time data
- Assess ventilation performance
- Assess mitigation strategies such as effectiveness of portable air cleaners
- Detect sudden changes in IAQ
- Track long-term trends
Air pollution monitors (monitors) can transmit near real-time results on one or more air pollutants or environmental factors to computers, phones, or cloud databases. Other monitoring and testing options include professional, calibrated handheld devices that provide data only at a specific moment in time and professional performance testing and in-depth analysis.
Limitations in Using IAQ Monitors
The American Lung Association recognizes several limitations in the use of IAQ monitors in schools:
- There are no nationally recognized standards or recommendations on the use of monitors in schools.
- There are no nationwide thresholds and standards for most indoor air pollutants.
Currently, nationally accepted indoor concentration recommendations exist for radon, temperature, and relative humidity. “It is important to understand that there are currently no widely accepted air concentration limits for most pollutants indoor[s] and therefore levels that trigger an alert of a potential problem are determined by the manufacturer of the monitor”.1 - Limited information is available on how well some monitors detect air pollutants indoors.
- There is variability in accuracy among monitors.
“There is limited information on the accuracy and precision of low-cost air pollutant monitors currently available in the marketplace. The accuracy (measure of closeness to what is actually in air) and precision (measure of how well each air reading repeats) of some monitors can be impacted by a number of factors such as where the monitor is placed in the indoor space, time in use, methods of processing the data, temperature, and relative humidity, as well as the presence of multiple contaminants in the air. In addition, the accuracy and precision of pollutant detecting monitors can also vary across manufacturers as well as within product lines made by the same company.”1 - Monitors do not give a complete representation of IAQ and only detect pollutants or environmental factors for which they are designed in locations where they are placed and at times when they are in operation.
- Monitors cannot replace highly trained professionals with calibrated, hand-held equipment to conduct professional testing.
Monitors may complement and should be used in concert with IAQ best practices of 1) source control, 2) ventilation, and 3) air cleaning/filtration in helping to improve a school building’s IAQ. These IAQ best practices in schools are outside the scope of this document but can be found in such resources EPA’s Improving Air Quality webpage and the American Lung Association’s Indoor Air at Home, Work and School webpage. The data from these monitors can be tracked, analyzed, compiled, and shared. Data may contribute to decision-making when responding to IAQ issues and communicating and planning with school leadership.
Improving Indoor Air Quality: The 3 Step Approach
Benefits of IAQ Monitoring
The American Lung Association recognizes several benefits in the use of monitors in schools:
- Baseline and routine surveillance screening for levels of specific air pollutants and/or environmental factors.
- Identifying the potential need to take action to improve IAQ.
- Evaluating the efficacy of recent school improvements, such as upgraded HVAC systems or in-room HEPA air cleaners.
- Providing data for planning and future facilities maintenance, repairs, replacements, or upgrades.
- Comparing indoor pollutant levels to outdoors to help determine whether outdoor air is affecting indoor air quality.
- Establishing a baseline of indoor air pollutant levels to identify changes over time and support future decision-making.
IAQ Monitoring Guidance for Schools
The American Lung Association’s Indoor Air Quality Monitoring Guidance for Schools is designed as a checklist for your school as it plans for the use of air quality monitors. It is based on national standards and recommendations from the Environmental Protection Agency (EPA), American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), and Underwriters Laboratories (UL) and clearly cited throughout this document. This guidance is also consistent with the September 2026 released New York School Environmental Health Program Indoor Air Quality Monitoring Tool Program.2 Where no national standards or recommendations exist, that is also clearly noted within this guide.
Getting Started
Planning Your Monitoring Program
Managing and Using Monitoring Data
When Additional Support Is Needed
Parameters, Prioritization, Thresholds, Interpretation, Recommended Action Pathway, and Reporting
Parameter: Carbon Dioxide (CO2)
Priority: Essential
Reason for Monitoring: EPA suggests using CO2 as an indicator of airflow, to help identify insufficient ventilation.
Source of CO2: Human respiration is the primary source of CO2 in normally occupied classrooms.
Health Impact: In the classroom, elevated CO2 is linked to sleepiness, headaches, reduced concentration, and lower academic performance.
Action Thresholds
| Reading | Interpretation | Recommended Action |
|---|---|---|
<800 ppm | Excellent | Continue monitoring |
<1000 ppm | Acceptable | Continue monitoring |
1000-1499 ppm | Elevated | Investigate ventilation |
1500-1999 ppm | High | Investigate priority ventilation/corrective action |
2000+ ppm | Very High | Significant ventilation concern/act promptly |
Source for recommendations: New York State School Environmental Health Program,2 EPA,3 CDC,10 UL11
NOTE: ASHRAE and Minnesota Department of Health7 recommend ventilation of 15cfm of outdoor air per person
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
|
Parameter: Carbon Monoxide (CO)
Priority: Optional
Source of CO: CO results from incomplete combustion of carbon-containing fuels. Sources in and around schools include propane- or gas-powered HVAC units, water heaters, stoves, construction, cleaning, landscaping equipment, and vehicles.
Health Impact: CO can cause dizziness, confusion, impaired vision, or flu-like symptoms. High levels can lead to loss of consciousness or even death. Prolonged low-level exposure may have long-term health effects.
Action Thresholds
| Reading | Interpretation | Recommended Action |
|---|---|---|
0 to 2 ppm | Good: Typical background indoor levels | Continue: monitoring |
2 to 5 ppm | Fair: Minor but a source is likely | Watch: Look for source/trend |
5 to 9 ppm | Poor: Indicative of combustion source that should be identified and addressed. | Investigate: Address source; if unable to identify, ventilate affected area, address with professional assistance |
>9 ppm to <35 ppm | Greater urgency | Action: Ventilate affected area if not evacuated. Conduct immediate investigation and abatement; if unable to do so, declare emergency. |
>35 ppm through UL2034 alarm conditions | Emergency | Action: Immediately evacuate building. Engage health professionals to evaluate occupants. Address the hazard with professional assistance. |
Source for recommendations: World Health Organization set health-based indoor CO guidelines:9
- 8.7 ppm for 8-hour average
- 26 ppm for 1-hour average
CDC set indoor worker CO exposure recommendations:10
- 35 ppm for 8-hour
Indoor CO concentrations should remain as low as reasonably achievable.
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
If any level exceeds 2 ppm, full printout of the days’ time-stamped values should be available for the permanent record. |
Additional Considerations
The EPA National Ambient Air Quality Standards8 for CO apply to outdoor ambient air, not directly to classroom indoor air. Caution should be taken not to compare outdoor PM regulations to indoor PM concentrations.
- 9 ppm for 8-hour average
- 35 ppm for 1-hour average.
Parameter: Indoor Particulate Matter (PM2.5)
Priority: Essential
Sources of indoor PM2.5 include:
- Outdoor air
- Wildfire smoke
- Outdoor traffic
- Combustion bi-products
- Printing
- Dust
- Cooking
- Art activities
- Cleaning
- Construction resuspension
Health Impacts
Exposure is linked to:
- Eye, nose, and throat irritation
- Coughing, wheezing, chest tightness, and shortness of breath
- Increased asthma and other respiratory symptoms
- Reduced lung function
- Increased respiratory infections, risk of heart attacks
- Increased development and worsening of COPD
- Lung cancer
- Reduced concentration, academic performance
Action Thresholds
Source for recommendations: New York State School Environmental Health Program PM2.5 guidelines are:2
- <15 µg/m³
- 15-35 µg/m³
- >35 µg/m³
Proposed guidelines for PM2.5 indoors:
| Reading | Interpretation | Recommended Action |
|---|---|---|
0–15 µg/m³ while occupied | Generally low | Continue monitoring |
16-25 µg/m³ while occupied | Elevated | Watch: Look for source/trend |
26-35 µg/m³ while occupied | High | Investigate and consider mitigation |
>35 µg/m³ while occupied | Very high** | Action: Prompt investigation/ mitigation |
**This should not be interpreted as a safe indoor limit. Rather, indoor thresholds require context. For example, someone could be vacuuming during the unoccupied conditions while the HVAC is on recirculate mode, causing a very high reading. The important part of this guidance is % of occupied time above action threshold.
If indoor PM2.5 is elevated:
- Check outdoor ambient air quality levels
- Check for wildfire smoke and other outdoor sources of PM pollution
- Minimize indoor particle-generating activities
- Ensure doors and windows are closed
- Check HVAC filtration
- Consider portable HEPA air cleaners
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
|
Additional considerations
EPA specifically recommends PM2.5 sensors during wildfire events to identify trends and evaluate whether interventions are reducing indoor PM2.5.
The EPA National Ambient Air Quality Standard for PM2.5 applies to 24-hour outdoor ambient air, not directly to classroom indoor air.
Parameter: Outdoor PM2.5
Priority: Recommended as comparison
Outdoor monitors can provide information about background conditions or outdoor contaminant sources that may impact the IAQ in the school. For example, you can compare indoor air PM2.5 with outdoor PM2.5 to provide clues (not causation) of the source.
Airnow.gov may also provide useful information regarding local ambient air quality.
Sources of outdoor PM2.5 include:
- Wildfire and wood smoke
- Vehicle exhaust
- Agricultural activities
- Construction and road dust
- Industrial facilities and power plants
Health Impacts:
Exposure is linked to:
- Eye, nose, and throat irritation
- Coughing, wheezing, chest tightness, and shortness of breath
- Increased asthma and other respiratory symptoms
- Reduced lung function
- Increased respiratory infections, risk of heart attacks
- Increased development and worsening of COPD
- Lung cancer
- Reduced concentration, academic performance
Action Thresholds
The EPA National Ambient Air Quality Standard for PM2.5 applies to 24-hour outdoor ambient air, not directly to classroom indoor air.
24-hour concentration stated as Air Quality Index:
| Reading | Interpretation | Recommended Action |
|---|---|---|
0-50 | Good | Continue monitoring |
51-100 | Moderate | Watch: Look for source/trend |
101-150 | Unhealthy for sensitive groups | Investigate and consider mitigation |
151-200 | Unhealthy | Investigate and consider mitigation |
201-300 | Very unhealthy | Action: Prompt investigation/ mitigation. Look for outdoor and indoor sources. |
301-500 | Hazardous | Action: Emergency conditions; avoid all physical activity outdoors. Sensitive groups should remain indoors. Keep indoor particle levels low. |
>500 | Hazardous | Action: Emergency conditions; avoid all physical activity outdoors. Sensitive groups should remain indoors. Keep indoor particle levels low. |
If outdoor PM2.5 is elevated:
- Check outdoor ambient air quality
- Check wildfire smoke
- Check HVAC filtration
- Check doors/windows
- Consider portable HEPA air cleaners
- Minimize indoor particle-generating activities
How to Document the Report
| For schoolwide report daily: | School building report |
|---|---|
|
|
Additional Considerations
EPA and others provide guidance for recess, physical education, field trips, and athletics based on Air Quality Index and wildfire smoke.
- EPA's Air Quality and Outdoor Activity Guidance for Schools
- Minnesota Outdoor Air Quality Guidance for Schools and Childcare
- Oregon guidance for youth outdoor activities during wildfire smoke, air pollution events
Parameter: Radon
Priority: Essential
Radon measurement in schools is required in some states
Source: Radon is a naturally occurring radioactive gas produced by the breakdown of uranium in soil, rock, and groundwater. It can enter buildings through cracks and openings in foundations and accumulate indoors.
Health Impacts: Radon is the second leading cause of lung cancer in the United States, and the leading cause among those who have never smoked. Children are known to be more sensitive to radiation, so high radon in the school environment should be detected and mitigated. Radon can be a long-term hazard for school staff who regularly occupy what may be areas of highest risk.
Action Thresholds
| Reading | Interpretation | Recommended Action |
|---|---|---|
<2.0 pCi/L | Good – not "safe" but typical levels found indoors | Continue retesting—at least every 5 years or as required by law |
2.0 – 3.9 pCi/L | Fair—minor but a source is likely | Consider mitigation if confirmed since more exposure poses more risk |
≥4.0 - < 19.9 pCi/L | Elevated – indicative of source that should be identified and mitigated | Confirm result and mitigate problem with professional assistance |
≥20 - < 99.9 pCi/L | Urgency | Action – Confirm result while simultaneously arranging for prompt mitigation. Retest every 2 years after mitigation. |
≥100.0 pCi/L | Emergency | ACTION – Immediately relocate occupants from affected area(s). Address the hazard promptly with professional assistance. Retest every 2 years after mitigation. |
Source for recommendations: EPA5
Additional Recommendations:
The Lung Association recommends that professional consensus standards be followed for testing and mitigation of schools.
For more information on radon measurement in schools, see the Lung Association’s Radon Measurement Guidance for Schools.
Parameter: Relative Humidity (RH)
Priority: Essential
Reason for Monitoring: RH plays a key role in classroom comfort and health.
Source and Health Impacts:
RH over 60% promotes mold, mildew, dust mites, and bacterial growth. This can cause allergies, respiratory (breathing) problems, and bad odors.
RH below 30% can cause dry eyes and skin, sore throat, irritated sinuses, and nosebleeds.
Action Thresholds
Source for recommendations:
ASHRAE’s preferred school operating range 30-60%4
New York State Environmental Health Program recommends:2
| Reading | Interpretation | Recommended Action |
|---|---|---|
45% - 55% | Excellent | Continue monitoring |
Between 30-45% or | Good | Watch: Look for source/trend |
<30% or >60% | Needs improvement | Investigate and consider mitigation to improve RH. Flag and document:
|
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
|
Additional Recommendations:
A monitor should not be used to diagnose mold.
The school should conduct a physical building investigation and repair/correct the source of water intrusion, if elevated humidity is accompanied by:
- water intrusion,
- condensation,
- musty odors,
- visible mold, or
- wet building materials.
Parameter: Temperature
Priority: Essential
Source:
- Outdoor weather (extreme heat or cold)
- Solar heat gains from direct sunlight or insufficient shading
- HVAC system issues
- Inadequate ventilation or airflow
- Poor building insulation or air leads
- Internal heat sources (high occupancy, computers, lighting)
- Control or thermostat problems
Health Impacts:
- Heat stress, dehydration, and headaches
- Cold-related discomfort, shivering, and reduced dexterity
- Difficulty concentrating and reduced learning performance
- Fatigue, irritability, and decreased comfort
- Increased absenteeism and health complaints
- Exacerbation of exiting health conditions
Action Thresholds
Source for recommendations:
Preferred school operating range 68–78°F (ASHRAE and EPA).6
New York School Environmental Health Program recommends a range from 68°F to 80°F.2
| Reading | Interpretation | Recommended Action |
|---|---|---|
68°F to 72°F | Excellent | Continue monitoring |
65°F to <68°F or >72°F to 80°F | Good | Watch |
<65°F or >80°F | Needs improvement | Investigate and consider mitigation Flag:
|
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
|
Parameter: Total Volatile Organic Compounds (TVOC)
Priority: Optional
Source: VOCs can be released from building materials, cleaning products, and stored paints and chemicals, 3D printers.
Health Impacts:
- Eye, nose, and throat irritation
- Headaches
- Dizziness
- Asthma symptoms or flare-ups
- Fatigue and difficulty concentrating
- Nausea or discomfort from strong odors
Action Thresholds
Source for recommendations:
There are no current standards for TVOC.
| Reading | Interpretation | Recommended Action |
|---|---|---|
“An indoor air level of 500 µg/m³ is … consistent with the use of low-emitting materials and the presence of a well-designed HVAC providing adequate ventilation volume.”11 TVOC is a combined estimate of many VOCs. It does not identify specific chemicals or determine whether a health-based limit has been exceeded. NOTE: TVOC can be reported in ppb (parts per billion) or µg/m 3 (micrograms per cubic meter). Some monitors display both. There is no single exact conversation between these two measurements. | Do not use TVOC as a stand-alone pass/fail metric. ASHRAE specifically states that VOC monitoring should be carefully applied. | If TVOC is monitored, consider using the data:
|
How to Document the Report
| For each classroom report daily: | Example Report Documentation |
|---|---|
| Classroom #204
|
Additional Considerations
Areas in schools with VOCs should:
- Contain only approved materials, properly stored, for the work or study to be done. Toolkit for Safe Chemical Management in K-12 Schools | US EPA)
- Be well-documented as to their contents, with Safety Data Sheets's for all materials properly available, with staff trained on their use.
- Be properly ventilated to avoid vapors entering occupied classrooms.
- Regular inspection of VOCs and other chemicals should be considered.
If any reason exists to suspect a problem and if the source is not easily found and addressed, then a professional evaluation may be indicated.